| Product Information |
| Product name |
Air Rover XL120DA |
| National Stock Number (NSN) |
4120-01-511-8212 |
| Performance Specifications |
| Cooling capacity Btu @ 67-95°F and 80% RH |
140,000 Btu/hr |
| Operating conditions |
55°F to 105°F |
| Optional heating capacity |
30 kW (102,000 Btu/hr) |
| Air flow (CFM) cooling mode |
4000 evap, 7000 cond. |
| Humidity removed at 60% RH (gal/hr) |
9.6 gal/hr |
| Electrical System |
| Voltage |
460 VAC |
| Phase |
3 phase |
| Power (kw) @ 67-95°F and 80% RH |
17.0 |
| Current (Amps) |
34.4 |
| Circuit breaker size |
50 |
| NEMA plug configuration |
Hard wired |
| Supply wire size |
#8 |
| Physical Characteristics |
| Dimensions (H x W x D), inches |
66 x 34 x 78 |
| Weight, unit (lbs) |
1015 |
| Weight, shipping (lbs) |
1200 |
| Supply duct size (inches) |
20 in. |
| Return duct duct size (inches) |
20 in. |
| Quantity of directional air supply nozzles |
6-9, or 2 x 20" duct takeoffs |
| Sound level (dB), with duct |
68 |
| Fan type, evaporator |
Belt drive |
| Fan type, condenser |
Belt drive |
| Condensate recovery tank capacity (gal) |
Condensate pump |
| Refrigerant type |
R-22 |
| Refrigerant charge |
290 oz |
| Standard Features |
| Heavy duty 18 ga. precision sheet metal cabinet |
| Durable electrostatic powdercoat finish |
| High-efficiency Copeland® Scroll compressor |
| Hot gas bypass for frost control |
| Heavy duty motors with thermal overload |
| Low voltage circuitry for remote temp control |
| Digital thermostat |
| External site glass and gauge with charging ports |
| Lanced aluminum fin, rifled copper coils |
| Chrome handles for maneuverability |
| Four ball-bearing casters (two with brakes) |
| Options |
| Low ambient control |
Enables operation of cooling mode when outside air is less than 50° F through electronic outdoor motor control. |
| Electric heat |
Adds heating elements for a true HVAC system |
| Re-heat modules |
Humidity control and mold remediation |
| HEPA filter |
Enables removal of extremely small particles from the supply air. This option includes the HEPA filter, pre-filter, and a motor and pulley upgrade. |
| Johnson controls |
Senses return air temperature for fan speed selection. (*Available on direct drive units only) |
| Precision temperature control |
Allows the unit to operate at a set temperature and hold that temperature to within +/- 1.5° F (1° C). Model PC1 uses a Johnson Control system and can operate down to 55° F. Model PC2 uses a microprocesser control system and can operate down to 50° F with a reduced air flow. PC2 is designed for use in conjunction with backoffice environmental control systems. |
| Condensate pump |
Provides automatic moisture removal |
| Humidifier |
The humidifier option includes a high capacity electronic steam humidifier, contactor, and unit mounted control system with humidistat, sensor, and circuit breakers for unit and humidifier. (*It is strongly recommended that units with humidifiers have a condensate removal pump) |
| Accessories |
| Supply air plenum |
Installation accessory for ducting the supply air of an Air Rover HVAC system |
| Return air plenum |
Installation accessory for ducting the return air of an Air Rover HVAC system |
| Ceilpak |
Deployment of condenser intake/exhaust into airspace above a suspended ceiling |
| Roofpak |
Deployment of condenser intake/exhaust through the roof |
| Wallpak |
Deployment of condenser intake/exhaust through a window or wall opening |
| Condenser duct |
Two pieces of 8 ft. standard, non-insulated condenser duct for ducting of the condenser or evaporator air |
| Industrial duct - standard |
Industrial strength non-insulated duct for ducting of the condenser or evaporator air |
| Industrial duct - insulated |
Industrial strength insulated duct for ducting of the condenser or evaporator air |